Mall of America: measuring rooftop DX coils

In October 2026 we went up on the roof at Mall of America to measure the DX evaporator coils in its rooftop air handling units, so the replacements could be specified and quoted to fit the units as they are today.

Looking into a rooftop air handler through an open access panel at Mall of America

The units

The air handlers on the Mall of America roof are large units. Inside, the cooling coils are stacked in banks, one above another, with a drain pan between each bank. Getting to them means opening access panels and working inside the unit.

Coils this size are not something you order from a nameplate photo. Before anything can be quoted, someone has to see how each bank sits in the unit and how it will come out.

Stacked DX evaporator coil banks with drain pans between them inside a rooftop air handler

What we found

Each unit carries stacked DX evaporator coil banks, with refrigerant suction lines running above them and intermediate drain pans and support rails between the banks.

The drain pans and rails under the coils showed rust and standing water. That is worth noting on any coil job: the condition of what the coil sits on affects how the replacement is installed, not just what is built.

Tape measure across the fin face of a DX coil, counting fins per inch

What we measured

  • Face size of each bank

    Fin height and fin length, measured inside the casing for every coil bank.

  • Rows and fins per inch

    Rows deep in the direction of airflow, and fins counted over a measured inch on the coil face.

  • Circuiting and distributors

    The expansion valves, distributors and feeder tubes on each coil, so the replacement circuiting matches the system.

  • Connections and headers

    Suction and liquid connection sizes and where they sit, so the new coils line up with the existing piping.

  • Casing, rails and access

    Casing depth and flanges, the support rails, and the path each coil takes out of the unit and the new one takes in.

Expansion valves and refrigerant distributors feeding the circuits of a large DX coil

Why measure in person

A large DX coil can feed dozens of refrigerant circuits through several expansion valves and distributors. With coils this size and this many circuits, measuring in person lets us confirm the circuiting, the distributor and feeder arrangement, and how each bank comes out of the unit, before anything is quoted.

Onsite measuring visits are available in the Upper Midwest, scheduled case by case. Everywhere else, the measuring guide and worksheets cover the same ground.

Looking into a rooftop air handler through an open access panel at Mall of America

Where it stands

We measured the coils and quoted the replacements. Every coil is built to order in the USA by our manufacturing partners, and nothing is built until the drawing and quote are approved.

More on this coil type: DX evaporator coil replacement.

Large rooftop coils to replace?

Send the unit nameplate and a few photos. If the job is in the Upper Midwest and needs eyes on the coil, ask about a site visit.