How hand is determined
Most manufacturers determine hand standing on the entering-air side of the coil, facing it, with the airflow at your back. If the supply and return connections are on your right, it is a right-hand coil. On your left, left hand.
Not every manufacturer uses the same convention, and drawings are sometimes viewed from the other side. That is why we confirm hand on the approval drawing before your coil is built, rather than relying on the word alone.
Why counterflow matters for water coils
Water coil capacities are rated with the water flowing against the air: on a cooling coil the coldest water enters on the leaving-air side, where the air is coldest. Piping a water coil the other way, parallel flow, reduces its capacity, sometimes significantly on deep coils.
If a water coil arrives the wrong hand
A wrong-hand water coil can sometimes be installed so the water still flows counter to the air, by turning the coil and swapping which header is the supply. The vent and drain may then sit in the wrong places, so a vent has to be added at the new high point. Whether this works depends on the header arrangement.
Call us before you try it. It is not an option for steam or DX coils, where drainage and refrigerant distribution depend on the coil's orientation.